FK 5-1-12
SHTG 1230 (FK 5-1-12) Clean Agent Fire Suppression System
Engineered total flooding system at 25, 42, 50, and 70 Bar — the most environmentally responsible clean agent option.
Engineered Total Flooding System
The SHTG 1230 (FK 5-1-12) system is an engineered total flooding fire suppression system, available at 25, 42, 50, and 70 Bar operating pressure. With zero ozone depletion potential and a Global Warming Potential below 1, it is the most environmentally responsible clean agent system available — discharging as a clear, non-conductive vapor that leaves no residue.
Available Operating Pressures
25 Bar
362 psi
DOT welded cylinders (16.7L–369L). Standard DOT pressure for existing infrastructure.
42 Bar
609 psi
Widest range — welded (16.6L→453L) and seamless (15L→180L). Standard TPED/ISO installations.
50 Bar
725 psi
Seamless (15L→180L). Extended pipe runs for medium-complexity layouts.
70 Bar
1015 psi
Seamless (15L→180L). Maximum pressure rating for space-constrained installations.
Key Benefits
- Eco-Friendly Leader: ODP = 0 and GWP <1 — the cleanest environmental profile available.
- Sensitive Electronics Protection: Electrically non-conductive — prevents short circuits.
- Industrial Applications: Highly effective against flammable liquids (Class B).
- Minimal Cleanup: Leaves virtually zero residue — operations resume immediately.
- Safe for Occupied Spaces: Suitable for normally occupied areas up to 10%.
- Large-Scale Capability: Welded cylinders up to 453L hold up to 507 kg of agent.
Certifications
UL certification covers the 25, 42 and 50 Bar systems; 70 Bar is pending. FM Approval covers the 25 Bar systems only. Contact us for the latest status.
Operating Pressures
Cylinder Range
25 / 42 / 50 / 70 Bar
Cylinder Range
25 Bar362 psiDOT Welded Cylinders — DOT 4BW500
DOT Welded Cylinders — DOT 4BW500
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 16.7 | 1" | 8.4 | 18.6 | 17.3 |
| 28.8 | 1" | 14.4 | 32.0 | 24.9 |
| 52 | 2" | 26.0 | 58.0 | 52.4 |
| 80 | 2" | 40.0 | 89.4 | 61.0 |
| 106 | 2" | 53.0 | 118.5 | 78.6 |
| 150 | 2" | 75.0 | 167.8 | 100.1 |
| 180 | 2" | 90.0 | 201.4 | 116.3 |
| 240 | 2" | 120.0 | 268.5 | 156.5 |
| 369 | 3" | 184.5 | 412.9 | 241.3 |
42 Bar609 psiWelded Cylinders — TPED EN13322-1 / EN14208-1 · Seamless Cylinders — ISO 9809 (TPED)
Welded Cylinders — TPED EN13322-1 / EN14208-1
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 16.6 | 1" | 8.4 | 18.6 | 17.3 |
| 28.3 | 1" | 14.2 | 31.7 | 24.9 |
| 52 | 2" | 26.1 | 58.2 | 52.4 |
| 80 | 2" | 40.1 | 89.6 | 61.0 |
| 106 | 2" | 53.1 | 118.7 | 78.6 |
| 150 | 2" | 75.1 | 168.0 | 100.1 |
| 180 | 2" | 90.1 | 201.6 | 116.3 |
| 240 | 2" | 120.1 | 268.8 | 156.5 |
| 369 | 3" | 184.6 | 413.2 | 241.3 |
| 453 | 3" | 226.6 | 507.3 | 323.9 |
Seamless Cylinders — ISO 9809 (TPED)
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 15 | 1" | 7.6 | 16.8 | 27.0 |
| 30 | 1" | 15.1 | 33.6 | 43.5 |
| 50 | 1" | 25.1 | 56.0 | 70.0 |
| 80 | 2" | 40.1 | 89.6 | 99.5 |
| 120 | 2" | 60.1 | 134.4 | 102 |
| 150 | 2" | 75.1 | 168.0 | 115 |
| 180 | 2" | 90.1 | 201.6 | 130 |
50 Bar725 psiSeamless Cylinders — ISO 9809 (TPED)
Seamless Cylinders — ISO 9809 (TPED)
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 15 | 1" | 7.6 | 16.8 | 27.0 |
| 30 | 1" | 15.1 | 33.6 | 43.5 |
| 50 | 1" | 25.1 | 56.0 | 70.0 |
| 80 | 2" | 40.1 | 89.6 | 99.5 |
| 120 | 2" | 60.1 | 134.4 | 102 |
| 150 | 2" | 75.1 | 168.0 | 115 |
| 180 | 2" | 90.1 | 201.6 | 130 |
70 Bar1015 psiSeamless Cylinders — ISO 9809 (TPED)
Seamless Cylinders — ISO 9809 (TPED)
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 15 | 1" | 7.6 | 16.8 | 27.0 |
| 30 | 1" | 15.1 | 33.6 | 43.5 |
| 50 | 1" | 25.1 | 56.0 | 70.0 |
| 80 | 2" | 40.1 | 89.6 | 99.5 |
| 120 | 2" | 60.1 | 134.4 | 102 |
| 150 | 2" | 75.1 | 168.0 | 115 |
| 180 | 2" | 90.1 | 201.6 | 130 |


UL certification covers the 25, 42 and 50 Bar systems; 70 Bar is pending. FM Approval covers the 25 Bar systems only. Contact us for the latest status.
EPA SNAP listed agentsContact Us
Talk to an Expert
Please direct your inquiries to us and we will respond promptly.