HFC-227ea
SHTG 227 (HFC-227ea) Clean Agent Fire Suppression System
Engineered total flooding system available at 25, 42, 50, and 70 Bar — optimal protection across diverse environments.
Engineered Total Flooding System
The SHTG 227 (HFC-227ea) system is a pressurized, engineered total flooding fire suppression system super-pressurized with dry nitrogen, available at 25, 42, 50, and 70 Bar operating pressure. It suppresses Class A, B, and C hazards by absorbing heat (80%) and through direct chemical action (20%) — discharging in under 10 seconds without leaving residue.
Available Operating Pressures
25 Bar
362 psi
DOT welded cylinders (16.7L–369L). Standard DOT pressure for existing infrastructure.
42 Bar
609 psi
Widest range — welded (16.6L→453L) and seamless (15L→180L). Standard TPED/ISO installations.
50 Bar
725 psi
Seamless (15L→180L). Extended pipe runs for medium-complexity layouts.
70 Bar
1015 psi
Seamless (15L→180L). Maximum pressure rating for space-constrained installations.
Key Benefits
- Sensitive Electronics: Non-conductive discharge — no risk of short circuits in data centers, switchrooms, and server rooms.
- Flammable Liquids: Effective on Class B hazards in industrial settings.
- Zero Residue: No post-discharge cleanup — operations resume immediately.
- Safe for Occupants: NOAEL 9.0% v/v — suitable for normally occupied spaces.
- Scalable: Max fill up to 507 kg per cylinder for large-volume protection.
Certifications
UL certification covers the 25, 42 and 50 Bar systems; 70 Bar is pending. FM Approval covers the 25 Bar systems only. Contact us for the latest status.
Operating Pressures
Cylinder Range
25 / 42 / 50 / 70 Bar
Cylinder Range
25 Bar362 psiDOT Welded Cylinders — DOT 4BW500
DOT Welded Cylinders — DOT 4BW500
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 16.7 | 1" | 8.4 | 18.6 | 17.3 |
| 28.8 | 1" | 14.4 | 32.0 | 24.9 |
| 52 | 2" | 26.0 | 58.0 | 52.4 |
| 80 | 2" | 40.0 | 89.4 | 61.0 |
| 106 | 2" | 53.0 | 118.5 | 78.6 |
| 150 | 2" | 75.0 | 167.8 | 100.1 |
| 180 | 2" | 90.0 | 201.4 | 116.3 |
| 240 | 2" | 120.0 | 268.5 | 156.5 |
| 369 | 3" | 184.5 | 412.9 | 241.3 |
42 Bar609 psiWelded Cylinders — TPED EN13322-1 / EN14208-1 · Seamless Cylinders — ISO 9809 (TPED)
Welded Cylinders — TPED EN13322-1 / EN14208-1
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 16.6 | 1" | 8.4 | 18.6 | 17.3 |
| 28.3 | 1" | 14.2 | 31.7 | 24.9 |
| 52 | 2" | 26.1 | 58.2 | 52.4 |
| 80 | 2" | 40.1 | 89.6 | 61.0 |
| 106 | 2" | 53.1 | 118.7 | 78.6 |
| 150 | 2" | 75.1 | 168.0 | 100.1 |
| 180 | 2" | 90.1 | 201.6 | 116.3 |
| 240 | 2" | 120.1 | 268.8 | 156.5 |
| 369 | 3" | 184.6 | 413.2 | 241.3 |
| 453 | 3" | 226.6 | 507.3 | 323.9 |
Seamless Cylinders — ISO 9809 (TPED)
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 15 | 1" | 7.6 | 16.8 | 27.0 |
| 30 | 1" | 15.1 | 33.6 | 43.5 |
| 50 | 1" | 25.1 | 56.0 | 70.0 |
| 80 | 2" | 40.1 | 89.6 | 99.5 |
| 120 | 2" | 60.1 | 134.4 | 102 |
| 150 | 2" | 75.1 | 168.0 | 115 |
| 180 | 2" | 90.1 | 201.6 | 130 |
50 Bar725 psiSeamless Cylinders — ISO 9809 (TPED)
Seamless Cylinders — ISO 9809 (TPED)
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 15 | 1" | 7.6 | 16.8 | 27.0 |
| 30 | 1" | 15.1 | 33.6 | 43.5 |
| 50 | 1" | 25.1 | 56.0 | 70.0 |
| 80 | 2" | 40.1 | 89.6 | 99.5 |
| 120 | 2" | 60.1 | 134.4 | 102 |
| 150 | 2" | 75.1 | 168.0 | 115 |
| 180 | 2" | 90.1 | 201.6 | 130 |
70 Bar1015 psiSeamless Cylinders — ISO 9809 (TPED)
Seamless Cylinders — ISO 9809 (TPED)
| Size (L) | Valve (in) | Min Fill (kg) | Max Fill (kg) | Nominal Tare Weight (kg) |
|---|---|---|---|---|
| 15 | 1" | 7.6 | 16.8 | 27.0 |
| 30 | 1" | 15.1 | 33.6 | 43.5 |
| 50 | 1" | 25.1 | 56.0 | 70.0 |
| 80 | 2" | 40.1 | 89.6 | 99.5 |
| 120 | 2" | 60.1 | 134.4 | 102 |
| 150 | 2" | 75.1 | 168.0 | 115 |
| 180 | 2" | 90.1 | 201.6 | 130 |


UL certification covers the 25, 42 and 50 Bar systems; 70 Bar is pending. FM Approval covers the 25 Bar systems only. Contact us for the latest status.
EPA SNAP listed agentsContact Us
Talk to an Expert
Please direct your inquiries to us and we will respond promptly.